Applied Sciences (Switzerland), cilt.15, sa.7, 2025 (SCI-Expanded)
In recent years, PV power plants have been widely used on the roofs of commercial buildings with grid connections, primarily to enhance self-consumption in distributed energy systems. In addition, installing PV plants on commercial buildings’ roofs is becoming increasingly important, especially in crowded cities where land is limited. Since the Sun is an intermittent energy source, PV power plants cause frequency and voltage fluctuations in the grid. The way to avoid this problem is to install PV plants together with battery storage systems. Battery storage systems prevent frequency and voltage fluctuations in the grid and provide economic benefits. This article presents the sizing and techno-economic analysis of a factory building’s rooftop PV system with a battery. The amount of energy produced by the PV plant, PV temperature, and irradiation were recorded in a data logger obtained by various sensors. These real-time measurements were continuously collected and analyzed to evaluate system performance and assess seasonal variations.Load demand data were collected through an automatic meter reading system. The installed capacity of the PV power plant is 645 kW. The optimum battery capacity determined for this factory is 130 kW for 5 h. Techno-economic analysis was carried out using metrics such as the payback period, net present value, and levelized cost of energy. As a result of the analysis using various input variables, LCOE, NPV, and PBP were determined as 0.1467 $/kWh, 4918.3 $, and 7.03 years, respectively.